GPVN-40.5kV AC Lokoo Kiekie Voltage Vacuum Breaker Circuit Breaker
Kūlana Kūlohelohe
Kiʻekiʻe: 1000m(Maʻamau);hiki i ka 4500m no ke kauoha kūikawā;
Ka mahana wela: -25 ℃ ~+45 ℃;
ʻO ka haʻahaʻa pili: ka awelika o kēlā me kēia lā ≤95%, awelika mahina ≤90%;
Ka ikaika ōlaʻi: ≤8 degere;
ʻO nā manawa kūpono e hoʻokuʻu ʻia mai nā inflammables, explosives, corrosive a me ka haʻalulu nui.
Hoʻohālike
Hana Hana
1. Aia ma ka ʻaoʻao luna ke keʻena hoʻopau arc a ma ka ʻaoʻao lalo ka mīkini.He kūpono kēia ʻano no ka debug.
2. Paʻakikī insulating hale me ka hoʻohana 'ana i ka ea a me ka organic mea;ʻAno paʻakikī a me ke kaumaha liʻiliʻi.
3. ʻO ke keʻena hoʻopau arc-extinguish vacuum o Cutler-Hammer Company (USA) a me ka ZMD home no ka VCB.ʻO nā ʻano keʻena ʻelua e hoʻopau i ke arc ma ke kahua magnetic vertical a hōʻike ʻia me ka ʻoki haʻahaʻa a me ka hiki ke hoʻokuʻu ʻia me ka asymmetry.
4. He manuahi ka mīkini hana puna maʻalahi mai ka mālama ʻana i loko o 10000 mau manawa o ka hana.
5. Lead-screw propeller, maʻalahi a paʻa ka hana a me ka hiki ke hoʻopaʻa pono iā ia iho.
Hōʻike ʻenehana
ʻAʻole. | 'ikamu | Unite | ʻIkepili |
1 | Volta koho | kV | 36/38/40.5 |
2 | 1 min.ʻO ke alapine ikaika e kū i ka volta | kV | 95 (118, kaawale kaawale) |
3 | Kū'ē ka uila uila (peak) | kV | 185 (215 kaawale kaawale) |
4 | Kuhi ʻia i kēia manawa | A | 630,1250,1600,2000, 2500 |
5 | Hoʻoholo ʻia ka ʻauahi pōkole | kA | 20, 25, 31.5 |
6 | Hoʻoholo ʻia ka manawa pōkole e hana nei (peak) | kA | 50, 63, 80 |
7 | 4s i helu ʻia no ka manawa pōkole e kū i kēia manawa | kA | 20, 25, 31.5 |
8 | ʻO ke kiʻekiʻe i koho ʻia e kū i kēia manawa | kA | 50, 63, 80 |
9 | Ka helu hana ʻana | O-0.3s-CO -180s-CO | |
10 | ʻO ka wā hoʻomaha o ke au haʻi kaapuni pōkole i helu ʻia | Manawa | 30 |
11 | Ola mīkini | Manawa | 10000;20000 (no ke ʻano magnet) |
12 | Ua helu pinepine ʻia | Hz | 50/60 |
13 | Hoʻoholo ʻia ka haki ʻana o kēia manawa o ka panakō capacitor | A | 400 |
ʻO ka ʻenehana kikoʻī o ka mīkini mālama ʻana o ka mīkini hana
ʻAʻole. | Volta koho | Mana hoopuka helu | Volta hana maʻamau | |
HDZ-22301B | DC110V AC110V | DC220V AC220V | ≤230W | ʻO 85% -110% ka uila helu |